AKCP Battery Monitoring Sensor (BATTMON)
Battery Monitoring Sensor for monitoring the voltage, temperature, and current load for batteries and DC power systems.
- The temperature of the battery terminals
- The voltage output from batteries or panel array
- Current load on batteries or charging circuit
The Battery Monitoring Sensor is a simple, yet effective way to monitor a variety of battery types. Lead Acid, LiPoly, individual cells or banks of batteries. The sensor consists of a battery terminal temperature sensor, battery DC Voltage meter and a current transformer.
Check the battery system performance, such as charge/discharge status. This sensor aids in maintaining and monitoring battery health for generators and engines, backup UPS power and solar systems.
The Battery Monitoring Sensor monitors an individual cell or bank of batteries, as well as DC power systems like solar panel arrays. With Battery Monitoring Sensor, you can monitor:
Typical applications would be for battery monitoring, solar panel array, or generator starter batteries.
BATTMON - Technical Specification
Measurements | |
Power Rating | Input Voltage and Current ratings : Voltage: 0~60VDC (3 configurable ranges : 0~15V, 0~30V or 0~60V) Current: DC current via external CT + 50A (standard) + 100A + 200A + 400A + 500A + 600A + 800A + 1000A + 1500A |
Power Measurements | - Voltage (V) : +/-0.05% Full-Scale, error +/-0.05% Full-Scale - Current (A) : +/-0.05% Full-Scale, error +/-0.05% Full-Scale, Temperature Drift : +/-0.02%/°C - Power (W) : +/-0.05% resolution |
Environment monitoring | - Temperature sensor with 1 meter cable *range -40°C to +75°C |
Status Indication | LED indication for power LED indication for input presence |
Inputs | 1x sensor RJ45 Port Hardwired with following plugs : - Phoenix connector for voltage - Phoenix connector for temperature - Phoenix connector for external current transformer |
Interface | |
Communications cable | RJ-45 jack to sensor using UTP CAT5e/6 cable |
Power source | Powered by the sensorProbe+ familiy units. No additional power needed |
Power Consumption | |
Maximum Cable Length | Run length is 32 feet (10 meters) with approved low capacitance shielded cable or UTP |
Dimensions | 56 x 55 x 33.3 mm |
Mounting | DIN rail mounting Screw mounting |
Components | Manufactured using highly integrated, low power surface mount technology to ensure long term reliability. |
Operating Environment | Temperature : Min. -35° C - Max.80° C Humidity: Min. 20% - Max. 80% (Non-Condensing) |
MTBF | 1,400,000 Hours based on field experience with sensorProbe units. |
Important Note: | the BattMon sensor is not galvanically isolated, care must be taken regarding possible differential voltage potential issues - The BattMon sensor is only compatible with the sensorProbe+ platform units. - When plugging the first time or after upgrading a sensorProbe+ unit, the sensor's firmware might be upgraded by the unit and not be available right away. - Smart sensor upgrade can only be performed on the main 4 sensor ports of the SP+ - Correctly sized CT must be ordered with the BATTMON. CT size is set in production and can?t be changed. |
Sensor count | 4 |
Ordering Information
Product Model | Order Number | Description |
---|---|---|
Battery Monitoring Sensor & CT?s | ||
BATTMON | 944094 | Battery Monitoring Sensor (Voltage, temperature and current) CT Not included |
BAT-CT50 | 944095 | Battery Monitoring 0-50A CT |
BAT-CT100 | 944106 | Battery Monitoring 50-100A CT |
BAT-CT200 | 944107 | Battery Monitoring 100-200A CT |
BAT-CT400 | 944108 | Battery Monitoring 300-400A CT |
BAT-CT500 | Battery Monitoring 400-500A CT | |
BAT-CT600 | Battery Monitoring 500-600A CT | |
BAT-CT800 | Battery Monitoring 700-800A CT | |
BAT-CT1000 | Battery Monitoring 800-1000A CT | |
BAT-CT1500 | Battery Monitoring 1000-1500A CT | |
BAT-CT2000 | Battery Monitoring 1500-2000A CT |